DP Transmitter Level Measurement for Closed Tank – Wet Leg Method

 DP Transmitter Level Measurement for Closed Tank – Wet Leg Method

Simply when LP side of the DP transmitter is filled with liquid then we call it as Wet Leg & we apply Wet Leg Method for calculations

Y = H1 +H2 = 500 + 200 = 700 mm

At zero level (LRV) = pressure acting on HP leg – Pressure acting on LP leg

= H2 x SG1 – Y x SG2

= 200 x 0.9 – 700 x 1.0

= 180 – 700

= – 520 mmwc


At 100 % level (URV) = pressure acting on HP leg – Pressure acting on LP leg

= (H2+H1) x SG1 – Y x SG2

= (200 + 500) x 0.9 – 700 x 1.0

= 630 – 700

= -70 mmwc

Range = URV – LRV = -70 – (-520) = 450 mmwc

So, we have to set Lower Range Value (LRV) = -520 mmwc and Upper Range Value (URV) = -70 mmwc in the DP Transmitter using HART communicator.